Universal IS Pressure Transmitter UniTrans
Operation of Transmitters with Display
2266939.05 D/GB 06/2006
Subject to change due to technical modifications. © Copyright WIKA Alexander Wiegand GmbH & Co. KG / Germany
WIKA Alexander Wiegand GmbH & Co. KG · Alexander-Wiegand-Str. · 63911 Klingenberg · (09372) 132 - 710 · Fax - 706 · E-mail: support-tronic@wika.de · www.wika.de
127
Example:
Level 100 %: 4000 mm
Density: 1 g/cm3
Density correction: 0.9 g/cm3
Span end point:
The span (end-point) must be re-calibrated (with or without pressure) to 4000 mm in
order to prevent a 4000 mm level tank from being overfilled.
Please check the following if "Wrong Entry" appears in the Evaluation
menu:
whether or not more than 32 value pairs are entered in the table for tank
linearization (please note: P 0 and P 31 are fixed at 0% and 100% re-
spectively)
whether or not an existing height value was tried to be stored again
Please enter correct values.
A change or correction in the density causes a change in the span end-
point’s unit of measure (mm, m, inch, feet). The span end-point must be
re-calibrated when changing the medium to be measured (due to a
change in density).
4
000 mm 1 g/cm
3
0.9 g/cm
3
-
--------------------------------------------------- -
4444 mm
=
Important