WIKA operating instructions process transmitter, model UPT-2x
14068347.01 06/2014 GB/D
GB
8.Congurationwithoutdisplayandoperatingunit
8. Congurationwithoutdisplayandoperatingunit
8.1 Performingamountingcorrection(oset)
The mounting correction corrects a zero oset in the output signal by dening a new
zero point. The zero oset is caused by the mounting position.
Correction range: ±20 % of maximum measuring range
Required tool: Multimeter (ammeter)
1. Screw o the case head cover and pull out the push-on cap.
2. Press [Zero] for approx. 2 s (e.g. with measuring tip of a multimeter).
Mounting correction successful: Control diode lights up for 2 s.
Mounting correction unsuccessful: Control diode blinks 5 times.
3. Check the output signal as follows.
CAUTION!
Incorrect connection.
A short circuit will destroy the process transmitter.
- Ensure that the multimeter does not come into contact with the positive
power supply terminal.
Set the multimeter to current measurement.
Connect the positive measuring line of the multimeter to the test contact.
Connect the negative measuring line of the multimeter to the negative power
supply terminal.
Control diode
Mounting correction, [Zero] key
Test contact
Positive power supply terminal +
Negative power supply terminal