Wika DPT-10 Bedienungsanleitung Seite 87

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 96
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 86
The status byte corresponds to prole 3.0 "Probus PA Prole for Process Control Devices" coded.
The status "Measured value OK" is coded as 80 (hex) (Bit7 = 1, Bit6 0 = 0).
The measured value is transferred as a 32 bit oating point number in the IEEE-754 format.
Byte n
Byte n+1
Bit
7
VZ
Exponent
Bit
6
2
Bit
5
2
Bit
4
2
Bit
3
2
Bit
2
2
Bit
1
2
Bit
0
2
Bit
7
2
Bit
6
2
Bit
5
2
Bit
4
2
Bit
3
2
Bit
2
2
Bit
1
2
Bit
0
2
Sign
Bit
Significant
7
6 5
4
3
2 1
0
-1
-2
-3
-4
-5
-6 -7
Byte n+2
Byte n+3
Bit
7
2
Significant
Bit
6
2
Bit
5
2
Bit
4
2
Bit
3
2
Bit
2
2
Bit
1
2
Bit
0
2
Bit
7
2
Bit
6
2
Bit
5
2
Bit
4
2
Bit
3
2
Bit
2
2
Bit
1
2
Bit
0
2
Significant
-9
-10 -11
-12
-13
-14 -15
-16
-17
-18
-19
-20
-21
-22
-23
-8
Value = (-1)
VZ
2
(Exponent - 127)
(1 + Significant)
Fig. 58: Data format of the measured value
Coding of the status byte associated with the PA output value
Status
code
Description according to Pro-
bus standard
Possible cause
0x00 bad - non-specic Flash-Update active
0x04 bad - conguration error l Adjustment error
l Conguration error with PV-Scale (PV-Span too small)
l Unit irregularity
l Error in the linearization table
0x0C bad - sensor failure l Hardware error
l Converter error
l Leakage pulse error
l Trigger error
0x10 bad - sensor failure l Measured value generation error
l Temperature measurement error
0 x 1f bad - out of service constant "Out of Service" mode switched on
0 x 44 uncertain - last unstable value Failsafe replacement value (Failsafe-Mode = "Last value" and
already valid measured value since switching on)
0 x 48 uncertain substitute set l Switch on simulation
l Failsafe replacement value (Failsafe-Mode = "Fsafe value")
0 x 4c uncertain - initial value Failsafe replacement value (Failsafe-Mode = "Last valid value" and
no valid measured value since switching on)
0 x 51 uncertain - sensor; conversion
not accurate - low limited
Sensor value < lower limit
0 x 52 uncertain - sensor; conversion
not accurate - high limited
Sensor value > upper limit
0 x 80 good (non-cascade) - OK OK
0 x 84 good (non-cascade) - active
block alarm
Static revision (FB, TB) changed (10 sec. active, after the parameter
of the static category was written)
Dierential pressure transmitter DPT10 - metal measuring diaphragm Probus PA 87
11 Supplement
37245-EN-100120
Seitenansicht 86
1 2 ... 82 83 84 85 86 87 88 89 90 91 92 ... 95 96

Kommentare zu diesen Handbüchern

Keine Kommentare