If the adjustment ranges are exceeded, the message "Outside
parameter limits" appears. The editing procedure can be aborted with
[ESC] or the displayed limit value can be accepted with [OK].
This f unction enables reading out parameter adjustment data as well
as writing p arameter adjustment data into the sensor via the indicating
and adjustment module. A description of the function is available in the
operating instructions manual "Indicating and adjustment module".
The following data are read out or written with this function:
l Measured value presentation
l Adjustment
l Damping
l Linearisation curve
l Sensor-TAG
l Displayed value
l Display unit
l Scaling
l Current output
l Unit of measurement
l Language
The following safety-relevant data are not read out or written:
l SIL
l HART mode
l PIN
l Application
Copy sensor data
Copy sensor data?
Basic adjustment
If the "Reset" (sensor-specic basic adjustment) is carried out, the
sensor resets the values of the following menu items to the reset
values (see chart):
Menu section Function Reset value
Basic settings Unit of measurement bar
Temperature unit °C
Zero/Min. adjustment Measuring range begin
Span/Max. adjustment Measuring range end
Density 1 kg/l
Density unit kg/l
Damping 1 s
Linearisation linear
Copy sensor data
Reset
28 Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor 4 20 mA
6 Set up with the indicating and adjustment module
37300-EN-100302